4. CONFIGURATION
4.19.10. tMEr - Enabling Timer function
Acronym Scrolling message Submenu Attributes
tMEr TIMER ENABLE MODE R W
The parameter shows and sets enabling of the Timer function.
The Timer function is explained in detail in paragraph “5.11. Timer” on page 147.
Unit of measurement: -
Options: OFF = Timer disabled
ON.SEC = Timer enabled with time base Seconds
ON.MIN = Timer enabled with time base Minutes
4.19.11. MUL.SP - Enabling Multiset function
Acronym Scrolling message Submenu Attributes
MUL.SP MULTISET ENABLE MODE R W
The parameter shows and sets enabling of the Multiset function.
The MULTISET function is explained in detail in paragraph “5.12. Multiset, setpoint gradient” on page 149.
Unit of measurement: -
Options: OFF = Multiset disabled
On = Multiset enabled
4.19.12. SP.REM - Enabling the remote setpoint
Acronym Scrolling message Submenu Attributes
SP.REM REMOTE SP ENABLE MODE R W
The parameter shows and sets enabling and the type of the remote set point.
It is enabled in sub-menu I.SPR, parameter F.SPr = SETP
The remote set point must also be set as a function of the remote input F.SPr = SETP.
Remote mode is enabled from the keys, digital inputs, serial line or as Function Block output by setting the LO-RE option.
Unit of measurement: -
Options: OFF = Remote setpoint disabled
On = Remote setpoint enabled from analog input
SEr = Remote setpoint enabled from serial
4.19.13. SPr.t - Defining absolute or deviation remote setpoint
Acronym Scrolling message Submenu Attributes
SPr.t REMOTE SP TYPE MODE R W
The parameter shows and defines the setpoint as absolute or deviation.
The absolute remote setpoint replaces the local setpoint in the control.
The deviation remote setpoint is added algebraically to the local setpoint in the control.
The parameter appears only if the parameter SP.REM is different from OFF.
Unit of measurement: -
Options: ABSLT = Absolute remote setpoint
RELAT = Deviation remote setpoint
4.19.14. PROGR - Enabling the setpoint programmer
Acronym Scrolling message Submenu Attributes
PROGR PROGRAMMER ENABLE MODE R W

Table of Contents

Other manuals for gefran 650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran 650 and is the answer not in the manual?

gefran 650 Specifications

General IconGeneral
Brandgefran
Model650
CategoryTemperature Controller
LanguageEnglish

Related product manuals