80208G_MHW_650-1250-1350_01-2017_ENG
71
4. CONFIGURATION
4.8.5. LO.SPR - Minimum scale limit
Acronym Scrolling message Submenu Attributes
LO.SPR INPUT LOW LIMIT I.SPR R W
The parameter shows and sets the minimum scale limit.
Unit of measurement: Scale points or %, according to the remote setpoint input function selected
Options: -1999...9999 = In scale points referred to main input
-199.9...999.9 = In %, if the Power or RST.PW function was selected
4.8.6. HI.SPR - Maximum scale limit
Acronym Scrolling message Submenu Attributes
HI.SPR INPUT HIGH LIMIT I.SPR R W
The parameter shows and sets the maximum scale limit.
Unit of measurement: Scale points or %, according to the remote setpoint input function selected
Options: LO.SPR...9999 = In scale points referred to main input
LO.SPR...999.9 = In %, if the Power or RST.PW function was selected
4.8.7. OF.SPR - Scale offset correction
Acronym Scrolling message Submenu Attributes
OF.SPR INPUT OFFSET I.SPR R W
The parameter shows and sets the scale offset, i.e., the constant offset applied to all values measured by the input.
Unit of measurement: Scale points
Options: -999...999

Table of Contents

Other manuals for gefran 650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran 650 and is the answer not in the manual?

gefran 650 Specifications

General IconGeneral
Brandgefran
Model650
CategoryTemperature Controller
LanguageEnglish

Related product manuals