4. CONFIGURATION
4.9.1. FILT.1 - Digital filter
Acronym Scrolling message Submenu Attributes
FILT.1 DIGITAL FILTER I.CT1 R W
The parameter shows and sets the value of the digital filter time constant applied to the input for current transformer CT1.
Unit of measurement: Seconds
Options: 0.00...20.00
4.9.2. HI.CT1 - Maximum scale limit
Acronym Scrolling message Submenu Attributes
HI.CT1 INPUT HIGH LIMIT I.CT1 R W
The parameter shows and sets the maximum scale limit of the input for current transformer CT1.
Unit of measurement: A
Options: 0.0...100.0
4.9.3. OF.CT1 - Scale offset correction
Acronym Scrolling message Submenu Attributes
OF.CT1 INPUT OFFSET I.CT1 R W
The parameter shows and sets the scale offset, i.e., the constant offset applied to all values measured by current tran-
sformer CT1.
Unit of measurement: A
Options: -99.9...99.9