4.6.25. GROP.R - Group of parameters assigned to ramp
Acronym Scrolling message Submenu Attributes
GROP.R CONTROL PARAMETER GROUP DURING STEP RAMP PR.SPT R W
The parameter shows and sets the group of control parameters assigned to the step during the ramp.
PID.G.N is settable on the MODE submenu.
Unit of measurement: Number
Options: 0...PID.G.N = Number of group. If 0, parameters are those for controller settable on PID submenu
4.6.26. GROP.H - Group of parameters assigned to hold
Acronym Scrolling message Submenu Attributes
GROP.H CONTROL PARAMETER GROUP DURING STEP HOLD PR.SPT R W
The parameter shows and sets the group of control parameters assigned to the step during the hold.
PID.G.N is settable on the MODE submenu.
Unit of measurement: Number
Options: 0...PID.G.N = Number of group. If 0, parameters are those for controller settable on PID submenu
4.6.27. MSG.R - Message associated with the ramp
Acronym Scrolling message Submenu Attributes
MSG.R SCROLLING MESSAGE DURING STEP RAMP PR.SPT R W
The parameter displays and sets the message number associated with the step during the ramp, which is the message
that will appear on the display to scroll to the step you are configuring
More information on the scrolling message can be found in the section “3.1.2.2 Scrolling messages” on page 34.
Setting it to “0” will not show any messages.
Unit of measurement: ID number of the message
Options: 0...25
4.6.28. MSG.H - Message associated with the maintenance
Acronym Scrolling message Submenu Attributes
MSG.H SCROLLING MESSAGE DURING STEP HOLD PR.SPT R W
The parameter displays and sets the message number associated with the pitch during the maintenance, which is the
message that will appear on the display to scroll to the step you are configuring
More information on the scrolling message can be found in the section “3.1.2.2 Scrolling messages” on page 34.
Setting it to “0” will not show any messages.
Unit of measurement: ID number of the message
Options: 0...25