85
4. CONFIGURATION
4.13.1. S.TUNE - Enabling Self-Tuning
Acronym Scrolling message Submenu Attributes
S.TUNE SELF TUNING ENABLE PID R W
The parameter shows and sets enabling of Self-Tuning.
For more information on the Self-Tuning function, see paragraph “5.10.3. Self-Tuning” on page 145.
Unit of measurement: -
Options: OFF = Self-Tuning disabled
On = Self-Tuning enabled at next power-on only
On.AL = Self-Tuning enabled at all power-ons
4.13.2. SOFT.S - Enabling Soft-Start
Acronym Scrolling message Submenu Attributes
SOFT.S SOFT START ENABLE PID R W
The parameter shows and sets enabling of Soft-Start.
For more information on the Self-Start function, see paragraph “5.9. Soft-Start” on page 144.
This parameter appears only if S.TUNE = OFF.
Unit of measurement: -
Options: OFF = Soft-Start disabled
On = Soft-Start enabled at next power-on
4.13.3. SOFT.T - Soft-Start Time
Acronym Scrolling message Submenu Attributes
SOFT.T SOFT START TIME PID R W
The parameter shows and sets Soft-Start time, i.e., the time that the control output needs to reach the value required by
the PID.
This parameter appears only if SOFT.S = On.
Unit of measurement: Minutes
Options: 0.0...500.0
4.13.4. A.TUNE - Enabling Auto-Tuning
Acronym Scrolling message Submenu Attributes
A.TUNE AUTO TUNING ENABLE PID R W
The parameter shows and sets enabling of Auto-Tuning.
For more information on the Auto-Tuning function, see paragraph “5.10.4. Auto-Tuning” on page 146.
Unit of measurement: -
Options: OFF = Auto-Tuning disabled
On = Auto-Tuning enabled