Plated,2AWG,Hole Center Distance 15.875mm(5/8"),Short Tube,for
North American
Naked Crimping Terminal,OT,35mm^2,M8,Tin Plating,Naked Ring
Terminal
Wire,450/750V,227 IEC 02(RV)35mm^2,Blue,135A
Wire,450/750V,227 IEC 02(RV)35mm^2,black,135A
7.1.3 NE40E-X3 DC-Input Power Cable
If the power supply distance is longer than 35 m ( 114.83 ft ), you need to place the power
distribution cabinet near the NE40E. For cables to be selected, see Power Supply Distance
Shorter Than 15 m ( 49.21 ft ).
You need to prepare suitable cables according to the surveyed power supply distance between
the NE40E and the power distribution cabinet.
Power Supply Distance Shorter Than 15 m ( 49.21 ft )
If the power supply distance is shorter than 15 m ( 49.21 ft ), use the 16 mm^2 ( 0.02 in.^2 )
power cable to connect the NE40E and the power distribution cabinet.Table 7-7 lists the cable
terminals and cable types.
Table 7-7 Cable used when the power supply distance is shorter than 15 m ( 49.21 ft )
Naked Crimping Terminal,JG2,16mm^2,M6,95A,Tin Plated,for OEM
Naked Crimping Terminal,OT,16mm^2,M8,Tin Plating,Naked Ring
Terminal
Wire,450/750V,227 IEC 02(RV)16mm^2,blue,85A
Wire,450/750V,227 IEC 02(RV)16mm^2,black,85A
Power Supply Distance Longer Than 15 m ( 49.21 ft ) and Shorter Than 35 m
( 114.83 ft )
If the power supply distance is longer than 15 m ( 49.21 ft ) and shorter than 35 m ( 114.83 ft ),
use the 25 mm^2 ( 0.04 in.^2 ) power cable to connect in the NE40E and the power
distribution cabinet. Table 7-8 lists the cable terminals and cable types.