Parameter Name / value range / [default seng] Info
0x6073
(P324.00)
Max current
(Max current)
0.0 ... [200.0] ... 3000.0 %
Maximum overload current of the inverter.
100 % ≡ Motor rated current 0x6075 (P323.00)
If the current consumpon of the motor exceeds this current limit,
the inverter changes its dynamic behaviour, in order to counteract this
exceedance.
If the change in the dynamic behaviour carried out by the inverter
does not result in exing the overcurrent state, the inverter outputs
an error.
Note!
This parameter is not idencal to the so-called ulmate motor current
I
ULT
!
The ulmate motor current set in 0x2D46:001 (P353.01) is a limit
value for synchronous motors that serves to protect their magnets.
The value to be set here should always be considerably below the ul-
mate motor current!
0x2D88
(P104.00)
Motor current
(Motor current)
Read only: x.x A
Display des present current-r.m.s. value.
0x6078
(P103.00)
Current actual value
(Current actual)
Read only: x.x %
Display of the present motor current.
100 % ≡ Motor rated current 0x6075 (P323.00)
Motor control
Motor protecon
Current limits
167

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals