9.4.10 Service data objects
Service data objects (SDOs) make it possible to read and write all parameters of the inverter
via CANopen.
Details
•
Two independent SDO channels are provided at the same me. SDO channel 1 is always
acve. SDO channel 2 can be acvated via 0x2301:005 (P510.05).
•
An SDO is always transmied with conrmaon, i. e. the recepon of an SDO frame is
acknowledged by the receiver.
•
The ideners for SDO1 and SDO2 are generated from the basic idener (in compliance
with the "Predened Connecon Set") and the node address set:
Object Direcon Idener
to the device from the device
SDO1
l
Basic idener 0x600 + node address
l
Basic idener 0x580 + node address
SDO2
l
Basic idener 0x640 + node address
l
Basic idener 0x5C0 + node address
Structure of the SDO frame user data
The user data are shown in Motorola format:
1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte 7th byte 8th byte
Command Index Subindex Data 1 Data 2 Data 3 Data 4
See table below. LOW byte HIGH byte LOW word HIGH word
Address of the parameter to be read or wrien. LOW byte HIGH byte LOW byte HIGH byte
The following commands can be transmied or received for wring and reading the parame-
ters:
Command 1st byte Data length Info
hex dec
Write request 0x23 35 4 bytes Wring of a parameter to the inverter.
0x2B 43 2 bytes
0x2F 47 1 byte
0x21 33 Block
Write response 0x60 96 4 bytes Inverter acknowledges a write request.
Read request 0x40 64 4 bytes Reading of a parameter from the inverter.
Read response 0x43 67 4 bytes Inverter response to a read request with the current parameter value.
0x4B 75 2 bytes
0x4F 79 1 byte
0x41 65 Block
Error response 0x80 128 4 bytes Inverter response to the incorrect execuon of the read/write request.
More precisely, the command byte comprises the following informaon:
Command 1st byte
Command specier (cs) Toggle (t) Length* e s
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Write request 0 0 1 0 0/1 0/1 1 1
Write response 0 1 1 0 0 0 0 0
Read request 0 1 0 0 0 0 0 0
Read response 0 1 0 0 0/1 0/1 1 1
Error response 1 0 0 0 0 0 0 0
*Bit coding of the length: 00 = 4 bytes, 01 = 3 bytes, 10 = 2 bytes, 11 = 1 byte
e: expedited (shortened block service)
s: segmented (normal block service)
More commands are dened in the DS301 V4.02 CANopen specicaon (e. g. segmented
transfer).