12.1 Segment conguraon
Each step of a sequence can call a "segment". A segment contains, among other things preset
setpoints (speed setpoint, PID control value, torque setpoint), a combined acceleraon/decel-
eraon for the speed setpoint and oponally a conguraon for the digital and analog out-
puts.
Details
As a total, 8 segments and one end segment can be congured.
The sengs are only eecve if a sequence is acve and the respecve segment is execu-
ted.
Not all sengs are relevant for all operang modes. If, for instance, the PID control is not
used at all, no PID setpoint needs to be set for the segment.
The following gure shows the segment sengs relevant for the operang mode 0x6060
(P301.00) = "MS: Velocity mode [-2]".
The table below contains a short overview of the possible sengs for each segment.
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
t
t
t
10 V
0 V
0x400A:002
0x1234 0x5678 0xFFFF
NetWordOUT2
Seq. controlled [10]
Analog output
Seq. controlled [100]
Relay / digital output
End segment
t
Segment2
t
Segment1
t
End segmentSegment 2Segment 1
Frequency setpoint
Seng Info
Frequency setpoint
Only relevant for the operang mode 0x6060 (P301.00) = "MS: Velocity mode [-2]". direcon of rota-
on according to sign.
Acceleraon/deceleraon
Only relevant for operang mode 0x6060 (P301.00) = "MS: Velocity mode [-2]". The set me refers
to the acceleraon from standsll to the set maximum frequency. The deceleraon is eected with
the same ramp.
Time
Meaning for segment 1 ... 8:
Runme for the segment aer the expiry of which it is switched over to the next step of the
sequence. Only relevant for Sequencer mode 0x4025 (P800.00) = "Time operaon [1]" or "Time &
step operaon [3]".
Meaning for end segment:
Delay me for acvang the output states congured for the end segment.
Digital outputs
Oponally: Set digital outputs to a certain level for the execuon me of the segment.
Analog outputs
Oponally: Set analog outputs to an adjustable voltage value for the execuon me of the segment.
PID setpoint Only relevant if the PID control in 0x4020:001 (P600.01) is acvated.
4Conguring the process controller ^ 238
Torque setpoint Only relevant for operang mode 0x6060 (P301.00) = "MS: Torque mode [-1]".
4Torque control w/ freq. limit ^ 153
NetWordOUT2
Oponally: Set NetWordOUT2 data word for the execuon me of the segment to an adjustable
value. The NetWordOUT2 data word 0x400A:002 (P591.02) can be mapped to a network register to
transfer the set value as process date.
4Further process data ^ 196
In the following, all parameters relevant for the segment conguraon are given.
If the sequencer is acve, write accessed to all parameters are blocked that con-
cern the acve segment conguraon!
Sequencer
Segment conguraon
327

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals