13.3.3 Keypad setpoint source
The following funcon is used to select the keypad as setpoint source.
Precondions
A setpoint change-over to the keypad is only eected if no setpoint source with a higher prior-
ity has been selected. 4Priority of the setpoint sources^ 367
Parameter Name / value range / [default seng] Info
0x2631:016
(P400.16)
Funcon list: Acvate keypad setpoint
(Funcon list: Setp: Keypad)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Acvate keypad setpoint" funcon.
Trigger = TRUE: the keypad is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
The default keypad setpoint can be changed in keypad operang
mode via the arrow keys of the keypad.
0 Not connected
Keypad setpoint default seng
For the manual setpoint selecon via keypad the following default sengs are used:
0x2601:001 (P202.01): Keypad setpoints: Frequency setpoint
0x2601:002 (P202.02): Keypad setpoints: Process controller setpoint
The increment for keypad setpoints can be adapted in 0x2862 (P701.00) by pressing a keypad
arrow key once.
Example for operang mode
The analog input 1 is set as standard setpoint source.
Switch S1 starts the motor in forward direcon of rotaon. Switch S1 in the inial posion
stops the motor again.
Switch S2 switches the direcon of rotaon.
Switch S3 acvates the keypad as setpoint source. The keypad setpoint can be changed in
the operang mode via the navigaon keys and keypad keys.
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Reverse rotaonal direcon
Switch S3 Acvate keypad setpoint
Parameter Name Seng for this example
0x2601:001 (P202.01) Keypad setpoints: Frequency setpoint 20.0 Hz
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Digital input 2 [12]
0x2631:016 (P400.16) Acvate keypad setpoint Digital input 3 [13]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
Flexible I/O conguraon
Setpoint change-over
Keypad setpoint source
370

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals