8.7.2 Current limits
For the purpose of current limitaon, a maximum overload current can be set for the inverter.
If the current consumpon of the motor exceeds this current limit, the inverter changes its
dynamic behaviour, in order to counteract this exceedance.
Details
The maximum overload current of the inverter can be set in 0x6073 (P324.00).
Reference for the percentage seng of the maximum overload current is the rated motor
current set in 0x6075 (P323.00).
The actual motor current is displayed in 0x2D88 (P104.00).
If the change in the dynamic behaviour carried out by the inverter does not
result in exing the overcurrent state, the inverter outputs an error.
Load behaviour Impact
Overload during acceleraon in
motor mode
A longer me than is required for reaching the frequency setpoint is set.
Overload during deceleraon in
generator mode
A longer me than is required for reaching standsll is set.
Increasing load at constant fre-
quency
If the motor current limit value is reached:
The inverter reduces the eecve speed setpoint unl a stable working is set or an eecve speed setpoint
of 0 rpm is reached.
If the load is reduced, the inverter increases the eecve speed setpoint unl the setpoint speed is
reached or the load reaches the current limit value again.
When the generator current limit value is reached:
The inverter increases the eecve speed setpoint unl a stable working point is reached or up to the max-
imum permissible output frequency 0x2916 (P211.00).
If the load is reduced, the inverter reduces the eecve speed setpoint unl the setpoint speed is reached
or the load reaches the current limit value again.
If an abrupt load is building at the motor sha (e.g. drive is blocked), the overcurrent switch-o funcon may
respond.
Example: Overcurrent switch-o in case of a sudden load at the motor sha
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0 Hz
30 Hz
10 Hz
20 Hz
40 Hz
50 Hz
60 Hz
t
0 %
100 %
t
0x6073
Motor load
Frequency setpoint selection
Output frequency
Motor control
Motor protecon
Current limits
166

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals