8.1 Motor data
Optimisation of the control loopsOptimisation of motor controlSetting of motor data Motor control selection
The term "motor data" comprises all parameters only depending on the motor and only char-
acterising the electrical behaviour of the machine. Motor data are independent of the applica-
on in which the inverter and the motor are used.
Precondions
When you enter the motor nameplate data, take into account the phase connecon imple-
mented for the motor (star or delta connecon). Only enter the data applying to the connec-
on type selected.
Possible sengs
If a Lenze motor is connected to the inverter, you can simply select the used motor in the
engineering tool from the "motor catalog".
•
For details see chapter "Motor selecon from motor catalogue". ^ 144
Otherwise the motor data has to be set manually (see the following subchapter).
8.1.1 Manual seng of the motor data
If an external motor is connected to the inverter, the motor data must be set manually in the
following parameters according to the manufacturer informaon/motor data sheet.
Parameter Name / value range / [default seng] Info
0x2C01:001 Motor parameters: Number of pole pairs
•
Read only
Display of the number of pole pairs calculated from the rated speed and
rated frequency.
0x2C01:004
(P320.04)
Motor parameters: Rated speed
(Motor parameters: Rated speed)
Device for 50-Hz mains: 50 ... [1450] ... 50000 rpm
Device for 60-Hz mains: 50 ... [1750] ... 50000 rpm
General motor data.
Carry out sengs as specied by motor nameplate data.
Note!
When you enter the motor nameplate data, take into account the phase
connecon implemented for the motor (star or delta connecon). Only
enter the data applying to the connecon type selected.
0x2C01:005
(P320.05)
Motor parameters: Rated frequency
(Motor parameters: Rated frequency)
Device for 50-Hz mains: 1.0 ... [50.0] ... 1000.0 Hz
Device for 60-Hz mains: 1.0 ... [60.0] ... 1000.0 Hz
0x2C01:006
(P320.06)
Motor parameters: Rated power
(Motor parameters: Rated power)
0.00 ... [0.25]* ... 655.35 kW
* Default seng depending on the size.
0x2C01:007
(P320.07)
Motor parameters: Rated voltage
(Motor parameters: Rated voltage)
0 ... [230]* ... 65535 V
* Default seng depending on the size.
0x2C01:008
(P320.08)
Motor parameters: Cosine phi
(Motor parameters: Cosine phi)
0.00 ... [0.80] ... 1.00
0x6075
(P323.00)
Motor rated current
(Motor current)
0.001 ... [1.700]* ... 500.000 A
* Default seng depending on the size.
•
Seng can only be changed if the inverter is inhibi-
ted.
The rated motor current to be set here serves as a reference value for
dierent parameters with a seng/display of a current value in percent.
Example:
•
Motor rated current = 1.7 A
•
Max current 0x6073 (P324.00) = 200 % Motor rated current = 3.4 A
0x6076
(P325.00)
Motor rated torque
(Motor torque)
0.001 ... [1.650]* ... 4294967.295 Nm
* Default seng depending on the size.
•
Seng can only be changed if the inverter is inhibi-
ted.
The rated motor torque to be set here serves as a reference value for
dierent parameters with a seng/display of a torque value in percent.
Example:
•
Motor rated torque = 1.65 Nm
•
Max torque 0x6072 (P326.00) = 250 % Motor rated torque = 4.125 Nm
0x6080
(P322.00)
Max motor speed
(Max motor speed)
0 ... [6075] ... 480000 rpm
Limitaon of the maximum motor speed.
Motor control
Motor data
Manual seng of the motor data
114