8.1 Motor data
Optimisation of the control loopsOptimisation of motor controlSetting of motor data Motor control selection
The term "motor data" comprises all parameters only depending on the motor and only char-
acterising the electrical behaviour of the machine. Motor data are independent of the applica-
on in which the inverter and the motor are used.
Precondions
When you enter the motor nameplate data, take into account the phase connecon imple-
mented for the motor (star or delta connecon). Only enter the data applying to the connec-
on type selected.
Possible sengs
If a Lenze motor is connected to the inverter, you can simply select the used motor in the
engineering tool from the "motor catalog".
For details see chapter "Motor selecon from motor catalogue". ^ 144
Otherwise the motor data has to be set manually (see the following subchapter).
8.1.1 Manual seng of the motor data
If an external motor is connected to the inverter, the motor data must be set manually in the
following parameters according to the manufacturer informaon/motor data sheet.
Parameter Name / value range / [default seng] Info
0x2C01:001 Motor parameters: Number of pole pairs
Read only
Display of the number of pole pairs calculated from the rated speed and
rated frequency.
0x2C01:004
(P320.04)
Motor parameters: Rated speed
(Motor parameters: Rated speed)
Device for 50-Hz mains: 50 ... [1450] ... 50000 rpm
Device for 60-Hz mains: 50 ... [1750] ... 50000 rpm
General motor data.
Carry out sengs as specied by motor nameplate data.
Note!
When you enter the motor nameplate data, take into account the phase
connecon implemented for the motor (star or delta connecon). Only
enter the data applying to the connecon type selected.
0x2C01:005
(P320.05)
Motor parameters: Rated frequency
(Motor parameters: Rated frequency)
Device for 50-Hz mains: 1.0 ... [50.0] ... 1000.0 Hz
Device for 60-Hz mains: 1.0 ... [60.0] ... 1000.0 Hz
0x2C01:006
(P320.06)
Motor parameters: Rated power
(Motor parameters: Rated power)
0.00 ... [0.25]* ... 655.35 kW
* Default seng depending on the size.
0x2C01:007
(P320.07)
Motor parameters: Rated voltage
(Motor parameters: Rated voltage)
0 ... [230]* ... 65535 V
* Default seng depending on the size.
0x2C01:008
(P320.08)
Motor parameters: Cosine phi
(Motor parameters: Cosine phi)
0.00 ... [0.80] ... 1.00
0x6075
(P323.00)
Motor rated current
(Motor current)
0.001 ... [1.700]* ... 500.000 A
* Default seng depending on the size.
Seng can only be changed if the inverter is inhibi-
ted.
The rated motor current to be set here serves as a reference value for
dierent parameters with a seng/display of a current value in percent.
Example:
Motor rated current = 1.7 A
Max current 0x6073 (P324.00) = 200 % Motor rated current = 3.4 A
0x6076
(P325.00)
Motor rated torque
(Motor torque)
0.001 ... [1.650]* ... 4294967.295 Nm
* Default seng depending on the size.
Seng can only be changed if the inverter is inhibi-
ted.
The rated motor torque to be set here serves as a reference value for
dierent parameters with a seng/display of a torque value in percent.
Example:
Motor rated torque = 1.65 Nm
Max torque 0x6072 (P326.00) = 250 % Motor rated torque = 4.125 Nm
0x6080
(P322.00)
Max motor speed
(Max motor speed)
0 ... [6075] ... 480000 rpm
Limitaon of the maximum motor speed.
Motor control
Motor data
Manual seng of the motor data
114

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals