9.4.5 Diagnoscs
For the purpose of diagnoscs, the inverter provides several status words via which the CAN
bus status, the CAN bus controller status, and the status of dierent me monitoring func-
ons can be queried.
Parameter Name / value range / [default seng] Info
0x2307
(P515.00)
CANopen me-out status
(Time-out status)
Read only
Bit-coded status display of the CAN me monitoring funcons.
Bit 0 RPDO1-Timeout 1 ≡ RPDO1 was not received within the monitoring me or not with the
sync congured.
Status is reset automacally aer the RPDO has been received again.
Seng of monitoring me for RPDO1 in 0x1400:005 (P540.05).
Bit 1 RPDO2-Timeout 1 ≡ RPDO2 was not received within the monitoring me or not with the
sync congured.
Status is reset automacally aer the RPDO has been received again.
Seng of monitoring me for RPDO2 in 0x1401:005 (P541.05).
Bit 2 RPDO3-Timeout 1 ≡ RPDO3 was not received within the monitoring me or not with the
sync congured.
Status is reset automacally aer the RPDO has been received again.
Seng of monitoring me for RPDO3 in 0x1402:005 (P542.05).
Bit 8 Heartbeat-Timeout Consumer 1 1 ≡ within the "Heartbeat Consumer Time", no heartbeat telegram was
received from node 1 to be monitored.
Status can only be reset by mains switching or error reset.
"Heartbeat Consumer Time" seng in 0x1016:001 (P520.01).
Bit 9 Heartbeat-Timeout Consumer 2 1 ≡ within the "Heartbeat Consumer Time", no heartbeat telegram was
received from node 2 to be monitored.
Status can only be reset by mains switching or error reset.
"Heartbeat Consumer Time" seng in 0x1016:002 (P520.02).
Bit 10 Heartbeat-Timeout Consumer 3 1 ≡ within the "Heartbeat Consumer Time", no heartbeat telegram was
received from node 3 to be monitored.
Status can only be reset by mains switching or error reset.
"Heartbeat Consumer Time" seng in 0x1016:003 (P520.03).
Bit 11 Heartbeat-Timeout Consumer 4 1 ≡ within the "Heartbeat Consumer Time", no heartbeat telegram was
received from node 4 to be monitored.
Status can only be reset by mains switching or error reset.
"Heartbeat Consumer Time" seng in 0x1016:004 (P520.04).
0x2308
(P516.00)
CANopen status
(CANopen status)
Read only
Display of the current eldbus state
0 Inialisaon Fieldbus inialisaon acve.
The inialisaon is started automacally at mains connecon. During
this phase, the inverter us not involved in the data exchange process
on the CAN bus.
All CAN-relevant parameters are inialised with the saved sengs.
When the inialisaon process has been completed, the inverter
automacally adopts the "Pre-Operaonal" state.
1 Reset node "Reset Node" NMT command acve.
All parameters are inialised with the saved sengs (not only the
CAN-relevant parameters).
2 Reset communicaon "Reset Communicaon" NMT command acve.
Inialisaon of all CAN-relevant parameters with the values stored.
4 Stopped Only network management telegrams can be received.
5 Operaonal Parameter data and process data can be received. If dened, process
data is sent as well.
127 Pre-Operaonal Parameter data can be received, process data are ignored.
Conguring the network
CANopen
Diagnoscs
207

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals