Parameter Name / value range / [default seng] Info
0x2552:006
(P595.06)
Parameter access monitoring: Parameter Access Mon-
itoring-Status
(PAM monitoring: PAM status)
•
Read only
•
From version 04.00
Bit coded display of the status of parameter access monitoring.
Bit 0 Monitoring acvated 1 ≡ parameter access monitoring is acve.
Bit 1 Timeout 1 ≡ within the me-out me set in 0x2552:003 (P595.03), no successful
parameter write access to the "keep-alive register" 0x2552:002
(P595.02) was made.
0x2552:007
(P595.07)
Parameter access monitoring: WLAN reset me-out
me
(PAM monitoring: WLAN reset t.out)
0 ... [0] ... 65535 s
•
From version 05.00
Time aer which the WLAN network with the current sengs of the
WLAN parameters is restarted if no "keep alive" messages are received.
•
0 s = funcon deacvated (no WLAN restart).
•
With a seng > 0 s and a me-out, the control units sets 0x2440 =
"Restart with current values [1]".
9.2.6 Process data handling in case of error
If the inverter receives invalid process data, the inverter uses the process data received last
(valid). You can oponally set that the contents of the process data in the inverter are set to
the value "0" aer invalid process data has been received.
The seng in 0x24E5:001 is independent of the response selected in
0x2859:005 if invalid process data has been received!
If the applicaon requires that the drive keeps moving with the last valid proc-
ess data when receiving invalid process data, set the response "No response" or
"Warning" in 0x2859:005. Moreover, the selecon "Clear data [1]" must not be
set in 0x24E5:001. Deleng the process data would stop the motor.
Parameter Name / value range / [default seng] Info
0x24E5:001 Process data handling in case of error: Procedure Selecon which process data the inverter is to use aer receiving invalid
process data.
0 Keep last data The last valid process data of the master are used.
1 Clear data The contents of the process data in the inverter is set to the value "0".
9.3 Acyclic data exchange
The acyclic data exchange is normally used for transming parameter data the transmission
of which is not me-crical. Such parameter data are for example operang parameters,
motor data, and diagnosc informaon.
Details
•
The acyclic data exchange enables access to all parameters of the inverter.
•
For all communicaon protocols except Modbus, the parameter is addressed directly via
the index and subindex.
•
The parameter aribute list contains a list of all inverter parameters. This list in parcular
includes some informaon that is relevant to the reading and wring of parameters via the
network.
Conguring the network
Acyclic data exchange
203