11.11 Holding brake control
This funcon serves as a low-wear control of a holding brake. The holding is usually mounted
to the motor as an opon. The holding brake can be automacally released via the start com-
mand for the inverter or manually via an external control signal, for instance, by a higher-level
Controller. The interacon of higher-level Controller and holding brake is especially important
for vercal applicaons. Horizontal applicaons need a less demanding holding brake control.
Precondions
Observe that the holding brake is an important element of the machine's safety concept as
a whole. Therefore be sure to carry out commissioning of this system part with parcular
care!
Holding brakes are not intended for braking during operaon. The increased wear caused
by braking during operaon may destroy the holding brake prematurely!
The holding brake control itself only outputs a digital trigger for releasing the holding
brake. This trigger "Release holding brake [115]" must be assigned to a digital output or, in
the simplest case, to the relay when then switches the brake supply. 4Conguraon of
digital outputs ^ 415
If the holding brake is to be controlled via a digital output, the use of an addional relay or
power contactor is required. The digital output is not suited for direct control of a holding
brake.
If, instead of an electrically releasing (self-holding) holding brake, an electrically holding
(self-releasing) holding brake is to be controlled, a signal inversion for the digital output
used or for the relay is to be set! 4
Conguraon of digital outputs ^ 415
Parameter Name / value range / [default seng] Info
0x2634:001
(P420.01)
Digital outputs funcon: Relay
(Dig.out.funcon: Relay funcon)
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 415
Assignment of a trigger to the relay.
Trigger = FALSE: X9/NO-COM open and NC-COM closed.
Trigger = TRUE: X9/NO-COM closed and NC-COM open.
Notes:
An inversion set in 0x2635:001 (P421.01)is taken into consideraon
here.
51 Ready for operaon TRUE if inverter is ready for operaon (no error acve, no STO acve and
DC-bus voltage ok). Otherwise FALSE.
Addional funcons
Holding brake control
300

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals