5 Commissioning
5.1 Important notes
WARNING!
Incorrect wiring can cause unexpected states during the commissioning phase.
Possible consequence: death, severe injuries or damage to property
Check the following before switching on the mains voltage:
▶
Is the wiring complete and correct?
▶
Are there no short circuits and earth faults?
▶
Is the motor circuit conguraon (star/delta) adapted to the output voltage of the inverter?
▶
Is the motor connected in-phase (direcon of rotaon)?
▶
Does the "emergency stop" funcon of the enre plant operate correctly?
WARNING!
Incorrect sengs during commissioning may cause unexpected and dangerous motor and sys-
tem movements.
Possible consequence: death, severe injuries or damage to property
▶
Clear hazardous area.
▶
Observe safety instrucons and safety clearances.
Commissioning
Important notes
34