Parameter Name / value range / [default seng] Info
117 Motor phase failure TRUE if a motor phase failure has been detected. Otherwise FALSE.
4Motor phase failure detecon ^ 169
118 UPS operaon acve TRUE if UPS operaon is acve. Otherwise FALSE.
4UPS operaon ^ 318
155 Both STO channels not acve TRUE if safe inputs SIA and SIB = LOW (simultaneously). Otherwise
FALSE.
0x2635:001
(P421.01)
Inversion of digital outputs: Relay
(DO inversion: Relay inverted)
Relay inversion
0 Not inverted
1 Inverted
0x4018:003 Relay: Switch-o delay
0.000 ... [0.000] ... 65.535 s
Switch-o delay for the relay.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the relay.
0x4018:004 Relay: Switch-on delay
0.000 ... [0.000] ... 65.535 s
Switch-on delay for the relay.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the relay.
0x4018:005 Relay: Relay state
•
Read only
Display of the logic state of the relay.
0 FALSE
1 TRUE
0x4018:006 Relay: Trigger signal state
•
Read only
Display of the logic state of the trigger signal for the relay (without tak-
ing a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
0x4018:007 Relay: Switching cycles
•
Read only
Display of the previous relay switching cycles.
13.15.2 Digital output 1
Sengs for digital output 1.
Parameter Name / value range / [default seng] Info
0x2634:002
(P420.02)
Digital outputs funcon: Digital output 1
(Dig.out.funcon: DO1 funcon)
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 415
Assignment of a trigger to digital output 1.
Trigger = FALSE: X3/DO1 set to LOW level.
Trigger = TRUE: X3/DO1 set to HIGH level.
Notes:
•
An inversion set in 0x2635:002 (P421.02) is taken into consideraon
here.
115 Release holding brake
100 Sequencer controlled (from version 03.00) The control is executed via the sequencer (according to the congura-
on of the digital outputs for the current segment).
4Segment conguraon ^ 327
0x2635:002
(P421.02)
Inversion of digital outputs: Digital output 1
(DO inversion: DO1 inversion)
Inversion of digital output 1
0 Not inverted
1 Inverted
0x4016:003 Digital output 1: Cutout delay
0.000 ... [0.000] ... 65.535 s
Switch-o delay for digital output 1.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the digital output.
Flexible I/O conguraon
Conguraon of digital outputs
Relay
418