9.2.5 Parameter access monitoring (PAM)
The parameter access monitoring can be used as basic protecon against a control loss of the
inverter. Monitoring is triggered if a parameter write access to a certain index does not take
place at regular intervals via the established communicaon connecon.
Precondions
This monitoring only works when the network control is acvated.
Except for the keypad, the monitoring can be used for all communicaon connecons, for
instance:
•
PC/Engineering Tool <--> inverter with USB module
•
PC/Engineering Tool <--> inverter with WLAN module
•
Controller <--> network <--> inverter with network opon
Details
For monitoring purposes, a non-zero value must be wrien into the "Keep-alive register"
0x2552:002 (P595.02) at regular intervals. The rst write access with a non-zero value ac-
vates monitoring. The intervals between the write accesses must not be higher than the me-
out me set in 0x2552:003 (P595.03). If no parameter write access takes place within the
me-out me, monitoring is triggered: The response selected in 0x2552:005 (P595.05) takes
place and the acon selected in 0x2552:005 (P595.05). In addion, the status bit 1 in
0x2552:006 (P595.06) is set to "1".
The error status can be le by a normal "error reset". Since monitoring connues to be acve
and the me-out me is not reset by the error reset, the inverter immediately changes again
to the error status. In order to prevent his, you have the following opons:
a)
Restore communicaon exchange.
b)
Set the monitoring response in 0x2552:004 (P595.04) to "No response [0]" or "Warning
[1]".
c)
Change over to local or exible control.
Parameter Name / value range / [default seng] Info
0x2552:002
(P595.02)
Parameter access monitoring: Keep alive register
(PAM monitoring: Keep alive reg.)
0 ... [0] ... 65535
•
From version 04.00
Register for cyclic parameter write accesses for monitoring the commu-
nicaon link.
•
If the seng is non-zero, the monitoring is acve.
•
In order that the monitoring is not tripped, a non-zero value has to be
entered into this index at regular intervals. The temporal distances of
the write accesses must not be higher than the me-out me set in
0x2552:003 (P595.03).
0x2552:003
(P595.03)
Parameter access monitoring: Time-out me
(PAM monitoring: Time-out me)
0.0 ... [10.0] ... 6553.5 s
•
From version 04.00
Maximum permied me between two write accesses to the "keep-
alive-register".
In case of a me-out
•
the error response selected in 0x2552:004 (P595.04) is eected,
•
the acon selected in 0x2552:005 (P595.05) is eected,
•
the status bit 1 in 0x2552:006 (P595.06) is set to "1".
0x2552:004
(P595.04)
Parameter access monitoring: Reacon
(PAM monitoring: Reacon)
•
From version 04.00
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 169
Selecon of the response to the triggering of the parameter access mon-
itoring.
Associated error code:
•
33045 | 0x8115 - Time-out (PZÜ)
0 No response
0x2552:005
(P595.05)
Parameter access monitoring: Acon
(PAM monitoring: Acon)
•
From version 04.00
Selecon of the acon to be executed if the parameter access monitor-
ing is triggered.
0 No acon
1 Reserved
Conguring the network
Predened process data words
Parameter access monitoring (PAM)