8.2.1.4 V/f characterisc control - energy-saving (VFC Eco)
In case of the energy-saving V/f characterisc control (VFCplusEco). the motor voltage of the
inverter is detected by means of a linear characterisc as a funcon of the rotang eld fre-
quency or motor speed to be generated. Moreover, the motor is always driven in the opmal
eciency range via a cosϕ control and the resulng voltage reducon (reduced copper losses
in the asynchronous motor).
Details
Select energy-saving V/f characterisc control with linear characterisc:
1.
Motor control mode 0x2C00 (P300.00) = "V/f characterisc control (VFC open loop) [6]"
2.
V/f characterisc shape 0x2B00 (P302.00)= "Eco [3]"
Seng of the V/f characterisc:
•
Liming factors for the V/f characterisc are rated mains voltage 0x2540:001 (P208.01),
minimum frequency 0x2915 (P210.00) and maximum frequency 0x2916 (P211.00).
•
The base voltage 0x2B01:001 (P303.01) is usually set to the rated motor voltage (motor
nameplate data). The base voltage is preset to the rated mains voltage. This again is preset
according to the product key of the inverter. 4Mains voltage ^ 95
•
The base frequency 0x2B01:002 (P303.02) is usually set to the rated motor frequency
(motor nameplate data).
Eco eciency range:
•
The Eco eciency range (grey) is between the V/f-standard characterisc (black) and the
V/f Eco characterisc (green).
•
The V/f Eco characterisc (green) is dened by the operang point that results from the
minimum voltage 0x2B0D:001 (P330.01) and the base frequency 0x2B01:002 (P303.02).
•
The minimum voltage 0x2B0D:001 (P330.01) has to be set in percent with reference to the
base voltage 0x2B01:001 (P303.01).
0
[V]
[Hz]
0
20 %
100 %
0x2B01 001:
0x2B01 002:
0x2540 001:
0x29160x2915
0x2B0D 001:
The current output frequency can exceed the set maximum frequency if the
gain for the slip compensaon in 0x2B09:001 (P315.01) is set to a value higher
than 0.
Parameter Name / value range / [default seng] Info
0x2B0D:001
(P330.01)
VFC-ECO: Minimum voltage
(VFC-ECO: Min. voltage)
20 ... [20] ... 100 %
•
From version 02.00
Dening the operang point of the V/f eco characterisc. The V/f eco
characterisc denes the lower limit of the eco eciency range.
•
100 % ≡ Base voltage 0x2B01:001 (P303.01)
0x2B0D:006
(P330.06)
Cos phi actual value
(Cos Phi actual)
•
Read only
•
From version 02.00
0x2822:004
(P327.04)
Axis commands: Idenfy motor data (energized)
(Axis commands: Idenfy mot.)
0 ... [0] ... 1
1 = start automac idencaon of the motor data.
•
Inverter characteriscs, motor equivalent circuit diagram data and
controller sengs are idened and set automacally.
•
During the procedure, the motor is energised!
0x2822:005
(P327.05)
Axis commands: Calibrate motor data (non-energized)
(Axis commands: Calibrate mot.)
0 ... [0] ... 1
1 = start automac calibraon of the motor data.
•
A default inverter characterisc is loaded.
•
the motor equivalent circuit diagram data and controller sengs are
calculated on the basis of the currently set rated motor data.
•
The motor is not energised.
Motor control
Motor control selecon
V/f characterisc control (VFC)