8.2.1.4 V/f characterisc control - energy-saving (VFC Eco)
In case of the energy-saving V/f characterisc control (VFCplusEco). the motor voltage of the
inverter is detected by means of a linear characterisc as a funcon of the rotang eld fre-
quency or motor speed to be generated. Moreover, the motor is always driven in the opmal
eciency range via a cosϕ control and the resulng voltage reducon (reduced copper losses
in the asynchronous motor).
Details
Select energy-saving V/f characterisc control with linear characterisc:
1.
Motor control mode 0x2C00 (P300.00) = "V/f characterisc control (VFC open loop) [6]"
2.
V/f characterisc shape 0x2B00 (P302.00)= "Eco [3]"
Seng of the V/f characterisc:
Liming factors for the V/f characterisc are rated mains voltage 0x2540:001 (P208.01),
minimum frequency 0x2915 (P210.00) and maximum frequency 0x2916 (P211.00).
The base voltage 0x2B01:001 (P303.01) is usually set to the rated motor voltage (motor
nameplate data). The base voltage is preset to the rated mains voltage. This again is preset
according to the product key of the inverter. 4Mains voltage ^ 95
The base frequency 0x2B01:002 (P303.02) is usually set to the rated motor frequency
(motor nameplate data).
Eco eciency range:
The Eco eciency range (grey) is between the V/f-standard characterisc (black) and the
V/f Eco characterisc (green).
The V/f Eco characterisc (green) is dened by the operang point that results from the
minimum voltage 0x2B0D:001 (P330.01) and the base frequency 0x2B01:002 (P303.02).
The minimum voltage 0x2B0D:001 (P330.01) has to be set in percent with reference to the
base voltage 0x2B01:001 (P303.01).
0
[V]
[Hz]
0
20 %
100 %
0x2B01 001:
0x2B01 002:
0x2540 001:
0x29160x2915
0x2B0D 001:
The current output frequency can exceed the set maximum frequency if the
gain for the slip compensaon in 0x2B09:001 (P315.01) is set to a value higher
than 0.
Parameter Name / value range / [default seng] Info
0x2B0D:001
(P330.01)
VFC-ECO: Minimum voltage
(VFC-ECO: Min. voltage)
20 ... [20] ... 100 %
From version 02.00
Dening the operang point of the V/f eco characterisc. The V/f eco
characterisc denes the lower limit of the eco eciency range.
100 % ≡ Base voltage 0x2B01:001 (P303.01)
0x2B0D:006
(P330.06)
Cos phi actual value
(Cos Phi actual)
Read only
From version 02.00
0x2822:004
(P327.04)
Axis commands: Idenfy motor data (energized)
(Axis commands: Idenfy mot.)
0 ... [0] ... 1
1 = start automac idencaon of the motor data.
Inverter characteriscs, motor equivalent circuit diagram data and
controller sengs are idened and set automacally.
During the procedure, the motor is energised!
0x2822:005
(P327.05)
Axis commands: Calibrate motor data (non-energized)
(Axis commands: Calibrate mot.)
0 ... [0] ... 1
1 = start automac calibraon of the motor data.
A default inverter characterisc is loaded.
the motor equivalent circuit diagram data and controller sengs are
calculated on the basis of the currently set rated motor data.
The motor is not energised.
Motor control
Motor control selecon
V/f characterisc control (VFC)
120

Table of Contents

Other manuals for Lenze I51AE175B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175B and is the answer not in the manual?

Lenze I51AE175B Specifications

General IconGeneral
BrandLenze
ModelI51AE175B
CategoryInverter
LanguageEnglish

Related product manuals