Parameter Name / value range / [default seng] Info
0x2540:001
(P208.01)
Mains sengs: Rated mains voltage
(Mains sengs: Mains voltage)
•
Seng can only be changed if the inverter is inhibi-
ted.
Selecon of the mains voltage for actuang the inverter.
0 230 Ve
1 400 Ve
2 480 Ve
3 120 Ve
0x2540:002
(P208.02)
Mains sengs: Undervoltage warning threshold
(Mains sengs: LU warn. thresh.)
0 ... [0]* ... 800 V
* Default seng depending on the size.
Seng of the warning threshold for monitoring DC bus undervoltage.
•
If the DC bus voltage falls below the threshold set, the inverter out-
puts a warning.
•
The warning is reset with a hysteresis of 10 V.
0x2540:003
(P208.03)
Mains sengs: Undervoltage error threshold
(Mains sengs: LU error thresh.)
•
Read only: x V
Display of the xed error threshold for monitoring DC bus undervoltage.
•
If the DC-bus voltage falls below the threshold displayed, the "Fault"
response is triggered.
0x2540:004
(P208.04)
Mains sengs: Undervoltage reset threshold
(Mains sengs: LU reset thresh.)
•
Read only: x V
Display of the xed reset threshold for monitoring DC bus undervoltage.
0x2540:005
(P208.05)
Mains sengs: Overvoltage warning threshold
(Mains sengs: OU warn. thresh.)
0 ... [0]* ... 800 V
* Default seng depending on the size.
Seng of the warning threshold for monitoring DC bus overvoltage.
•
If the DC bus voltage exceeds the threshold set, the inverter outputs a
warning.
•
The warning is reset with a hysteresis of 10 V.
0x2540:006
(P208.06)
Mains sengs: Overvoltage error threshold
(Mains sengs: OU error thresh.)
•
Read only: x V
Display of the xed error threshold for monitoring the DC bus overvolt-
age.
•
If the DC-bus voltage exceeds the threshold displayed, the "Fault"
response is triggered.
0x2540:007
(P208.07)
Mains sengs: Overvoltage reset threshold
(Mains sengs: OU reset thresh.)
•
Read only: x V
Display of the xed reset threshold for monitoring DC bus overvoltage.
Basic seng
Mains voltage
96