4.2.4.2 Fusing and terminal data
Fuse data
Inverter I51AE137F
I51AE155F
I51AE175F
I51AE211F
I51AE215F
I51AE222F
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16
Circuit breaker
Characteriscs B
Max. rated current A 10 16
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16
Circuit breaker
Characteriscs B
Max. rated current A 10 16
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B
Fuse data
Inverter I51AE137F
I51AE155F
I51AE175F
I51AE211F
I51AE215F
I51AE222F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 480 V
31