12
TROUBLESHOOTING
12.3 Error Code List
12.3.11 Error codes returned to request source during communication with CPU module
12 - 223
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
12.3.11 Error codes returned to request source during communication with
CPU module
The Q series CPU module returns an error code to the request source if an error occurs at
a request of communication from GX Developer, intelligent function module or network
system.
POINT
This error code is not an error that is detected by the CPU module self-diagnosis
function, so it is not stored in the special relay (SD0).
When the request source is a GX Developer, a message or an error code is
displayed.
When the request source is an intelligent function module or network system, an
error is returned to the process that was requested.
The error contents of the error codes (4000H to 4FFFH) detected by the CPU module and
the messages displayed by the GX Developer are shown in Table12.12.
Table12.12 Error code
Error code
(Hexadecimal)
Error item Error details Corrective action
4000
H
Common error
Serial communication sum check error
Connect the serial communication cable correctly.
Take noise reduction measures.
4001
H
Unsupported request was executed.
Check the command data of the MC protocol, etc.
Check the CPU module model name selected in the
peripheral device.
4002
H
Unsupported request was executed.
Check the command data of the MC protocol, etc.
Check the CPU module model name selected in the
peripheral device.
4003
H
Command for which a global request cannot
be performed was executed.
Check the command data of the MC protocol, etc.
4004
H
Any operation for the CPU module is
prohibited by the system protect function
provided against the following events.
The system protect switch is ON.
The CPU module is starting.
Set the system protect switch of the CPU module to
OFF.
Perform operation again after the CPU module has
completed starting.
4005
H
The volume of data handled according to the
specified request is too large.
Check the command data of the MC protocol, etc.
4006
H
Serial communication could not be initialized.
Check with the external device maker for the support
condition.
Check the CPU module model name selected in the
peripheral device.
4008
H
The CPU module is BUSY.
(The buffer is not vacant).
After the free time has passed, reexecute the request.
4010
H
CPU mode
error
Since the CPU module is running, the request
contents cannot be executed.
Execute after setting the CPU module to STOP status.
4013
H
Since the CPU module is not in a STOP
status, the request contents cannot be
executed.
Execute after setting the CPU module to STOP status.