180 Parameters
06.118 LSU start inhibit
status word
(Only visible when IGBT supply unit control activated by
95.20)
This word specifies the source of the inhibiting condition that
is preventing the supply unit from starting.
See also section Control of a supply unit (LSU) (page 77),
and parameter group 60 DDCS communication.
This parameter is read-only.
-
0000h…FFFFh Start inhibit status word of supply unit. 1 = 1
07
07 System info
Information on drive hardware, firmware and application
program.
All parameters in this group are read-only.
07.03 Drive rating id Type of the drive/inverter unit. -
07.04 Firmware name Firmware identification.
The format is AINFX, where X denotes the control unit type
(2 = BCU-x2, 6 = ZCU-12/14).
-
07.05 Firmware version Version number of the firmware.
The format is A.BB.C.D, where A = major version, B = minor
version, C = patch (ie. firmware variant code), D = 0.
-
07.06 Loading package
name
Name of the firmware loading package.
The format is AINLX, where X denotes the control unit type
(2 = BCU-x2, 6 = ZCU-12/14).
-
07.07 Loading package
version
Version number of the firmware loading package. See
parameter 07.05.
-
07.08 Bootloader version Version number of the firmware bootloader. -
07.11 Cpu usage Microprocessor load in percent. -
0…100% Microprocessor load. 1 = 1%
07.13 PU logic version
number
Version number of the power unit logic.
The value of FFFF indicates that the version numbers of
parallel-connected power units are different. See the drive
information on the control panel.
-
No. Name/Value Description Def/FbEq16
Bit Name
0 Not ready run
1 Ctrl location changed
2SSW inhibit
3 Fault reset
4 Lost start enable
5 Lost run enable
6…8 Reserved
9 Charging overload
10…11 Reserved
12 Em Off2
13 Em Off3
14 Auto reset inhibit
15 Reserved