Parameters 323
Other Source selection (see Terms and abbreviations on page 148). -
33.64 Value counter 2
divider
Defines a divisor for value counter 2. The value of the
monitored signal is divided by this value before integration.
1.000
0.001 …
2147483.000
Divisor for value counter 2. -
33.65 Value counter 2
warn message
Selects the optional warning message for value counter 2. Value
counter 2
exceeded
Value counter 2
exceeded
A88B Value counter 2. The message text can be edited on
the control panel by choosing Menu – Settings – Edit texts.
5
Maintain motor
bearing
A880 Motor bearing.10
35
35 Motor thermal
protection
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section Motor thermal protection (page 116).
35.01 Motor estimated
temperature
Displays the motor temperature as estimated by the internal
motor thermal protection model (see parameters
35.50…35.55). The unit is selected by parameter 96.16 Unit
selection
This parameter is read-only.
-
-60 … 1000
°C or °F
Estimated motor temperature. 1 = 1°
35.02 Measured
temperature 1
Displays the temperature received through the source
defined by parameter 35.11 Temperature 1 source. The unit is
selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
Measured temperature 1. 1 = 1 unit
35.03 Measured
temperature 2
Displays the temperature received through the source
defined by parameter 35.21 Temperature 2 source. The unit
is selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
-60 … 1000 °C,
-76 … 1832 °F or
0…5000 ohm
Measured temperature 2. 1 = 1 unit
No. Name/Value Description Def/FbEq16