Parameters 501
99.19 Sine filter
capacitance
Defines the capacitance of a custom sine filter, ie. when
parameter 95.15 Special HW settings bit 3 is activated.
If the capacitors are star/wye-connected, enter the
capacitance of one leg
into the parameter.
If the capacitors are delta-connected, multiply the
capacitance of one leg
by 3 and enter the result into the
parameter.
Note: For an ABB sine filter (95.15 Special HW settings bit 1),
this parameter is set automatically and should not be
adjusted.
-
0.00 … 100000.00
µF
Capacitance of custom sine filter. 100 = 1 µF
200
200 Safety
FSO-xx settings.
This group contains parameters related to the optional FSO-xx safety functions module. For details on the
parameters in this group, refer to the documentation of the FSO-xx module.
No. Name/Value Description Def/FbEq16
M
Sine filter
3~
Drive
C
99.19 = C
C C
M
Sine filter
3~
Drive
CC
C
99.19 = 3 × C