EasyManuals Logo
Home>Delta>Controller>AH Series

Delta AH Series User Manual

Delta AH Series
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #137 background imageLoading...
Page #137 background image
Chapter 7 Motion Control Programming
7-11
7_
7.5.2 Axis Group State
9
Note1: The axis group moves by multi-axis motion control instructions.
Note2: Entering “ErrorStop” state when an error occurs on the axis group.
Note3: (1) When axis group is enabled and in ErrorStop state, the DFB_GroupReset becomes effective to switch group
states. (2) When axis group executes DFB_GroupReset in ErrorStop state and every axis of MC_Power is Enabled (ON),
the group is in Standbystate with all errors cleared and the group maintained; (3) When executing DFB_GroupReset in
ErrorStop, the speed of every axis must be 0 to clear the axis errors; however, the contact of Busy will be ON until every
axis speed in the group is 0 and all errors are cleared to reach Done.
Note4: (1) When axis group is not enabled, the DFB_GroupReset can switch group states.
(2) When axis group executes DFB_GroupReset in ErrorStop state and an axis of MC_Power is not Enabled, the group
state is Disabledwith all errors cleared and the group removed.
Note5: DFB_GroupDisable swiches the group state to Disabled.”
Note6: Group state changes to Standbywhen Done of DFB_GroupStop is True and Execute of DFB_GroupStop
changes to Fasle.
Note7: Group state enters to “ErrorStop” when one of the axis of MC_Power is removed during “Stopping”.
Note8: Group state switches to “ErrorStop” when executing
MC_GroupDisable, group motion functions (MC_GroupStop
not included) or a single-axis motion instruction is executed in Coordinatedstate.
Note9: Group state switches to “ErrorStop” when a single-axis motion control instruction is executed in Coordinated
state to remove an axis of MC_Power in the axis group.
Note10: If ‘StopMode=1’ in DFB_GroupStop: the execution pauses and when Execute”=TRUE, the axis group is in
“Stoppingand will change to Movingwhen “Execute”=FALSE

Table of Contents

Other manuals for Delta AH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AH Series and is the answer not in the manual?

Delta AH Series Specifications

General IconGeneral
BrandDelta
ModelAH Series
CategoryController
LanguageEnglish

Related product manuals