RRP: ED-DCX-4S-B chassis
127
Removal and Replacement Procedures (RRPs)
Verifying need for replacement
Verify that replacement of the chassis is necessary. Ensure that the
components are firmly seated when troubleshooting, and contact
your support provider with any questions about whether the chassis
should be replaced.
Any of the following events might indicate the need to replace the
chassis:
◆ Visible mechanical damage to the chassis, including damage to
sheet metal or card guides that prevents correct installation of a
blade.
◆ Bent or damaged connectors on the backplane (the surface inside
the chassis to which the blades connect).
◆ One or more components (such as a power supply, blower
assembly, port blade, control processor blade (CP8), core switch
blade (CR4S-8), or WWN card) do not function properly even
after the component was replaced.
◆ The psShow or fanShow commands continue to show a faulty
component even though the component was replaced.
◆ The slotShow command continues to show a faulty control
processor (CP8), core switch (CR4S-8), or port blade even though
the blade was replaced.
Recording critical ED-DCX-4S-B and SAN information
All commands must be entered from a CLI session (Telnet or serial) to
the active CP blade unless otherwise indicated.
Note: Run supportShow which includes all of the information in Table 13 on
page 128 and more.
For detailed information about Fabric OS commands, refer to the
Connectrix B Series Fabric OS Command Reference Guide. Use a checklist
provided in Table 13 on page 128 to ensure that all required
information is recorded.