4.4.2 SENSITIVE POWER SETTING GUIDELINES
For reverse and low forward power protection, if settings greater than 3% Pn are used, the phase angle errors of
suitable protection class curr
ent transformers will not result in any risk of maloperation. If settings of less than 3%
are used, however, we recommend that the current input is driven by a correctly loaded metering class current
transformer.
The sensitive power protection has a minimum setting accuracy of 0.5% Pn. It uses the In sensitive CT to calculate
single-phase active power. It also provides phase compensation to remove errors introduced by the primary input
transformers.