As can be seen from the diagram, the VTS function is inhibited if:
An All Poles Dead
DDB signal is present
Any phase overcurrent condition exists
A Negative Phase Sequence current exists
If the phase current changes over the period of 1 cycle
2.6 VTS ACCELERATION INDICATION LOGIC
Trip Command In
V0
2001
VTS Acc Ind
Figure 175: VTS Acceleration Indication Logic