Lockout Reset
CB Close
User Interface
V00513
Reclaim Complete
CB Open 3 ph
DT complete
Autoreclose Start
AR in Progress
Block Autoreclose
AR CB Unhealthy
CB Status Alarm
Reset lockout
Reset Lckout Alm
Lockout Alarm
Protection Lockt
Man No Checksync
CB Closed 3 ph
Main Protection Trip
Autoreclose Initiate
Main High Shots
SEF Protection Trip
Autoreclose Initiate
SEF High Shots
Reset Lockout by
Yes
AR Lockout
HMI Clear
&
&
&
S
R
Q
1
1
&
S
R
Q
Reset
Lockout
&
&
1
CB Cls Fail
Figure 159: Overall Lockout logic
AR lockout may also be due to a protection operation when the IED is in the Liv
e Line or Non-auto modes when the
setting Trip AR Inactive is set to Lockout. Autoreclose lockout can also be caused by a protection operation after
manual closing during the AR Inhibit Time when the Man Close on Flt setting is set to Lockout. This is shown as
follows:
Chapter 13 - Autoreclose P14x
302 P14xEd1-TM-EN-1