14. Thread down the threaded rod until the tip of the rod is approximately 1 inch inside the turnbuckle.
15. Insert the nuts and hand-tighten the nuts.
16. Repeat the previous three steps so that all assemblies are completely installed, as shown in the
previous illustration.
17. Tighten all the nuts to 40 ft-pounds.
The frame is now secured.
Considerations for Multiple System Installations
In a multi-frame installation, it is possible that a floor tile with cable cutouts (refer to “Cutting and
Placement of Floor Panels” on page 105) will bear two concentrated static loads up to 567 kg (1250 lbs)
per caster/leveler. Thus, the total concentrated load can be as high as 1134 kg (2500 lbs). Contact the
floor tile manufacturer or consult a structural engineer to ensure that the raised floor assembly can support
this load.
When you are integrating an Eserver pSeries 655 into an existing multiple-system environment, or when
adding additional systems to an installed Eserver pSeries 655, consider the following factors:
v Minimum aisle width
For multiple rows of systems containing one or more Eserver pSeries 655, the minimum aisle width in
the front of the system is 1194 mm (47 in.) and 838 mm (33 in.) in the rear of the system to allow room
to perform service operations. The minimum aisle width is in addition to the front and rear service
clearances of 1143 mm (45 in.) and 914 mm (36 in.) respectively. Service clearances are measured
from the edges of the frame (with doors open) to the nearest obstacle.
v Thermal interactions
Systems should be faced front-to-front and rear-to-rear to create cool and hot aisles to maintain
effective system thermal conditions, as shown in the following illustration.
Cool aisles need to be of sufficient width to support the airflow requirements of the installed systems as
indicated in Cooling Requirements on Page 90. The airflow per tile will be dependent on the underfloor
pressure and perforations in the tile. A typical underfloor pressure of 0.025 in. of water will supply
300-400 cfm through a 25% open 2 ft. by 2 ft. floor tile.
Chapter 2. Physical Characteristics of Systems 115