Magstar
®
MP 3575 Tape Library Dataserver Model L06
Dimensions
Height 991 mm 39 in.
Width 355 mm 14 in.
Depth 836 mm 37.9 in.
Weight
Maximum 71 kg 157 lbs
Electrical
Power source loading 0.175
(typical in kVA)
Voltage range (V ac) 100 to 127 or 200 to 240
Frequency (hertz) 50 or 60
Thermal output
(typical)
600 Btu/hr
Power requirements
(typical)
175 watts
Power factor 0.99
Maximum altitude 2135 m (7000 ft.)
Temperature
Requirements
Operating
16 to 32°C
(60 to 90°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity
Requirements
Operating Non-Operating
(Noncondensing) 8 to 80% 8 to 80%
Wet Bulb 26°C(79°F) 27°C(80°F)
Noise Emissions* Operating Idle
L
WAd
6.6 bels 5.6 bels
L
pAm
N/A N/A
<L
pA
>
m
47dBA 34dBA
Impulsive noise Yes Yes
Prominent discrete
tones
No No
Clearances Front Back Left Right
Install/Air Flow 76 mm (3 in) 76 mm (3 in) 76 mm (3 in) 76 mm (3 in)
Service Install so that it can be moved to an area providing 760 mm (30 in) on each side.
* See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
Chapter 6. Physical Characteristics of the 3000 Series 251