3490E Enhanced Magnetic Tape Subsystem E01 and E11
Dimensions E01 (Table Top)
Height 268 mm 10.8 in
Width 220 mm 8.8 in
Depth 801 mm 32.0 in
Dimensions E01 (Rack Mounted)
Height 336 mm 13.5 in
Width 220 mm 8.8 in
Depth 758 mm 30.3 in
Weight
E01 25.9 kg 57 lbs
E11 36.0 kg 80 lbs
Electrical
Power source loading
(typical in kVA)
E01 0.39
E11 0.39
Thermal Output (max) 540 Btu/hr
Temperature
Requirements
Operating
16 to 32°C
(60 to 90°F)
Non-Operating
10 to 40°C
(50 to 104°F)
Humidity
Requirements
Operating Non-Operating
(Noncondensing) 8 to 80 % 8 to 80 %
Wet Bulb 27°C (80.6°F) 27°C (80.6°F)
Noise Emissions* Operating Idle
E01 58 dBA 53 dBA
E11 58 dBA 53 dBA
Clearances Front Back Left Right
Service Install so that it can be moved to an area providing 760 mm (30 in) on each side.
* See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
244 Site and Hardware Planning Information