7025 Deskside 6F0 Series
Dimensions
Height 610 mm 24.0 in.
Width 483 mm 19.0 in.
Depth 728 mm 28.7 in.
Weight
Minimum configuration 70 kg 155 lbs.
Maximum configuration 95 kg 209 lbs.
Electrical
Power source loading typical in kVA 0.42
Power source loading maximum in kVA 0.63
Voltage range (V ac) 100 to 127 or 200 to 240 (autoranging)
Frequency (hertz) 50 or 60
Thermal output (typical) 1365 Btu/hr
Thermal output (maximum) 2048 Btu/hr
Power requirements (typical) 400 watts
Power requirements (maximum) 600 watts
Power factor 0.95
Inrush current³ 90 amps
Maximum altitude⁴ 2135 m (7000 ft.)
Temperature Requirements Operating
4, 5
10 to 38°C
(50 to 100°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity Requirements Operating⁴ Non-Operating
(Noncondensing) 8 to 80% 8 to 80%
Wet Bulb 23°C (73°F) 27°C (80°F)
Noise Emissions¹ Operating Idle
L
WAd
6.1 bels 5.9 bels
L
pAm
N/A N/A
<L
pA
>
m
43 dBA 40 dBA
Impulsive or prominent discrete tones No No
Clearances Front Back Left Right
Install/Air Flow² 76mm(3 in) 152mm(6 in) 51mm(2 in) 51mm(2 in)
Service Install so that it can be moved to an area providing 457 mm (18 in.) on the
front and 457 mm (18 in) on the left side.
Footprint
2
Width
585mm(23 in)
Depth
956mm(37.7 in)
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
4. A)Dry bulb temperature derating at high altitude: Upper limit temperature must be derated 1.0 deg C per 137 m
of elevation beyond 1295 m above sea level. (1 deg F per 250 ft above 4250 feet). B) Wet bulb temperature
derating at high altitude: Upper limit temperature must be derated 1 deg C per 274 m of elevation beyond 1372m
above sea level (1 deg F per 500 ft above 4500 feet).
5. For systems with FC 6134: 60/150 GB 16-bit 8mm Internal Tape Drive, the maximum operating temperature is
limited. For additional information about this limitation, refer to the following table.
Chapter 2. Physical Characteristics of Systems 59