Magstar MP 3575 Tape Library Dataserver Model L32
Dimensions
Height 1480 mm 58.3 in.
Width 1009 mm 39.7 in.
Depth 861 mm 33.9 in.
Weight
Maximum 203 kg 446 lbs
Electrical
Power source loading 0.45
(typical in kVA)
Voltage range (V ac) 100 to 127 or 200 to 240
Frequency (hertz) 50 or 60
Thermal output
(typical)
1200 Btu/hr
Power requirements
(typical)
350 watts
Power factor 0.78
Maximum altitude 2135 m (7000 ft.)
Temperature
Requirements
Operating
16 to 32°C
(60 to 90°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity
Requirements
Operating Non-Operating
(Noncondensing) 8 to 80% 8 to 80%
Wet Bulb 26°C(79°F) 27°C(80°F)
Noise Emissions* Operating Idle
L
WAd
6.8 bels 6.2 bels
L
pAm
N/A N/A
<L
pA
>
m
47dBA 34dBA
Impulsive noise Yes Yes
Prominent discrete
tones
No No
Clearances Front Back Left Right
Install/Air Flow 76 mm (3 in) 76 mm (3 in) 76 mm (3 in) 76 mm (3 in)
Service Install so that it can be moved to an area providing 760 mm (30 in) on each side.
* See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
Chapter 6. Physical Characteristics of the 3000 Series 255

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM RS/60000 Series and is the answer not in the manual?

IBM RS/60000 Series Specifications

General IconGeneral
BrandIBM
ModelRS/60000 Series
CategoryServer
LanguageEnglish

Related product manuals