Goodrive350 series high-performance multi-function inverter Chapter 4
-17-
Condensation is not allowed;
The max RH cannot exceed 60% in the environment where there are
corrosive gases.
The installation site should meet the following requirements.
Away from electromagnetic radiation sources;
Away from oil mist, corrosive gases and combustible gases;
Ensure foreign object like metal powder, dust, oil and water will not fall
into the inverter (do not install the inverter onto combustible object like
wood);
Away from radioactive substance and combustible objects;
Away from harmful gases and liquids;
Low salt content;
No direct sunlight
Below 1000m;
When the altitude exceeds 1000m, derate 1% for every additional
100m;
When the altitude exceeds 2000m, configure isolation transformer on
the input end of the inverter. It is recommended to keep the altitude below
5000m.
The max. amplitude of vibration should not exceed 5.8m/s
2
(0.6g)
Install the inverter vertically to ensure good heat dissipation effect
Note:
1. GD350 series inverter should be installed in a clean and well-ventilated environment based
on the IP level.
2. The cooling air must be clean enough and free from corrosive gases and conductive dust.
4.2.2 Installation direction
The inverter can be installed on the wall or in a cabinet.
The inverter must be installed vertically. Check the installation position according to following
requirements. See appendix for detailed outline dimensions.