Goodrive350 series high-performance multi-function inverter Chapter 5
-86-
Set value
Function
Description
PROFIBUS\CANopen
communication
17
Set value 2 of
PROFIBUS\CANopen
communication
-10001000, 1000 corresponds to 100.0%
18
Set value 1 of Ethernet
communication
-10001000, 1000 corresponds to 100.0%
19
Set value 2 of Ethernet
communication
-10001000, 1000 corresponds to 100.0%
20
Input value of high-speed
pulse HDIB
0.0050.00kHz
21
Reserved variable
22
Torque current (bipolar, 100%
corresponds to 10V)
0Two times of rated current of motor
23
Exciting current (100%
corresponds to 10V)
0One times of rated current of motor
24
Set frequency (bipolar)
0Max. output frequency
25
Ramps reference frequency
(bipolar)
0Max. output frequency
26
Running speed (bipolar)
0Max. output frequency
27
Reserved variable
3047
Reserved variable
Related parameter list:
Function
code
Name
Detailed parameter description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse
output
1: Open collector output
0
P06.14
AO1 output selection
0: Running frequency
1: Set frequency
2: Ramps reference frequency
3: Running speed
4: Output current (relative to inverter)
5: Output current (relative to motor)
6: Output voltage
7: Output power
8: Set torque value
9: Output torque
0
P06.15
Reserved variable
0
P06.16
HDO high-speed pulse output
0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive350 Series and is the answer not in the manual?

INVT Goodrive350 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive350 Series
CategoryDC Drives
LanguageEnglish

Related product manuals