Parameter Name / value range / [default seng] Info
0x4023:001
(P610.01)
PID sleep mode: Acvaon
(PID sleep mode: Acvaon)
Condion for acvang the idle state.
0 Disabled Idle state deacvated.
1 Output frequency < threshold 0x2B0E (P102.00)<0x4023:003 (P610.03)
(+ Delay me 0x4023:005 (P610.05))
2 Output frequency < threshold OR process
variable > feedback threshold
0x2B0E (P102.00)<0x4023:003 (P610.03)
(+ Delay me 0x4023:005 (P610.05))
OR
0x401F:002 (P121.02)>0x4023:004 (P610.04)
(+ Delay me 0x4023:005 (P610.05))
3 Output frequency < threshold OR process
variable < feedback threshold
0x2B0E (P102.00)<0x4023:003 (P610.03)
(+ Delay me 0x4023:005 (P610.05))
OR
0x401F:002 (P121.02)<0x4023:004 (P610.04)
(+ Delay me 0x4023:005 (P610.05))
0x4023:002
(P610.02)
PID sleep mode: Stop method
(PID sleep mode: Stop method)
Selecon of the stop method aer acvaon of the idle state.
0 Coasng The motor becomes torqueless (coasts down to standsll).
1 Deceleraon to standsll The motor is brought to a standsll with deceleraon me 1 (or deceler-
aon me 2, if acvated).
Deceleraon me 1 can be set in 0x2918 (P221.00).
Deceleraon me 2 can be set in 0x291A (P223.00).
4Frequency limits and ramp mes ^ 106
2 Stop method set The stop method set in 0x2838:003 (P203.03) is used.
0x4023:003
(P610.03)
PID sleep mode: Frequency threshold
(PID sleep mode: Freq. thresh.)
0.0 ... [0.0] ... 599.0 Hz
Frequency threshold for the acvaon of the idle state.
For comparing "output frequency < threshold" in case of selecon
1 ... 3 in 0x4023:001 (P610.01).
0x4023:004
(P610.04)
PID sleep mode: Feedback threshold
(PID sleep mode: Feedback thresh.)
-300.00 ... [0.00] ... 300.00 PID unit
Feedback threshold for the acvaon of the idle state.
For comparing "variable > feedback threshold" in case of selecon 2 in
0x4023:001 (P610.01).
For comparing "variable < feedback threshold" in case of selecon 3 in
0x4023:001 (P610.01).
0x4023:005
(P610.05)
PID sleep mode: Delay me
(PID sleep mode: Delay me)
0.0 ... [0.0] ... 300.0 s
Minimum me for which the respecve threshold must be underrun or
exceeded before the idle state is acvated.
0x4023:006
(P610.06)
PID sleep mode: Recovery
(PID sleep mode: Recovery)
Condion for terminang the idle state.
0 Setpoint > threshold OR system deviaon >
bandwidth
0x2B0E (P102.00) > 0x4023:003 (P610.03) (+ 2 Hz hysteresis)
OR
0x401F:007>0x4023:007 (P610.07)
1 Process variable < recovery threshold 0x401F:002 (P121.02) < 0x4023:008 (P610.08)
2 Process variable > recovery threshold 0x401F:002 (P121.02)>0x4023:008 (P610.08)
0x4023:007
(P610.07)
PID sleep mode: Bandwidth
(PID sleep mode: Bandwidth)
0.00 ... [0.00] ... 300.00 PID unit
Range around the process controller setpoint for terminang the idle
state.
0.00 = bandwidth deacvated.
0x4023:008
(P610.08)
PID sleep mode: Recovery threshold
(PID sleep mode: Recovery thresh.)
-300.00 ... [0.00] ... 300.00 PID unit
Terminaon threshold for idle state.
Conguring the process controller
Process controller - idle state and rinse funcon
Process controller idle state
246

Table of Contents