36
2-2. Specifications
I/O Conversion Characteristics
4. Performance Specifications of Link Unit
1) FP1 Transmitter Master Unit
2) FP1 I/O Link Unit
3) C-NET Adapter S1 Type
RS485 × 1 port, RS422 × 1 port
Between RS485 and RS422 interfaces
Interface
Conversion format
Item Description
64 points (Input: 32 points and Output: 32 points)
1 slot
Number of controllable
Input/Output points
Slot occupation
per FP1 I/O Link Unit
DescriptionItem
Interface
Data Transmission velocity
Number of controllable
I/O points
Transmission distance
RS485
0.5 M bps
64 points (Input: 32, Output: 32, setting when shipped)
When 2 transmitter master units are connected, the I/O points are as follows,
104 points (Input: 56, Output: 48, C14, C16 series)
144 points (Input: 80, Output: 64, C24, C40, C56 and C72 series)
Max. 700 m (with twisted pair cable)
DescriptionItem
5.0
2.5
500 1000
Analog
output
Digital input
(V)
(K)
0 to 5 V range
10
5
500 1000
Analog
output
Digital input
(V)
(K)
0 to 10 V range
20
10
500 1000
Analog
output
Digital input
(mA)
(K)
0 to 20 mA range
000