EasyManuals Logo
Home>Omron>Inverter>Varispeed E7

Omron Varispeed E7 User Manual

Omron Varispeed E7
321 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #129 background imageLoading...
Page #129 background image
5-22
îš‹ Option Parameters: F
Communications Option Cards: F6
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
F6-01
Operation selec-
tion after commu-
nications error
Set the stopping method for com-
munications errors.
0:Deceleration to stop using the
deceleration time in C1-02
1:Coast to stop
2:Emergency stop using the
deceleration time in C1-09
3:Continue operation
0 to 3 1 No A 3A2H –
F6-02
Option card
external fault
detection selec-
tion
0:Always detected
1:Detected only during operation
0 or 1 0 No A 3A3H –
F6-03
Option card
external fault
stopping method
0:Deceleration to stop using the
deceleration time in C1-02
1:Coast to stop
2:Emergency stop using the
deceleration time in C1-09
3:Continue operation
0 to 3 1 No A 3A4H –
F6-05
Current scaling
via communica-
tion option card
Sets the unit of the current monitor
0: Ampere
1: 100% 8192
0 or 1 0 No A 3A6H –