5-22
îš‹ Option Parameters: F
Communications Option Cards: F6
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
F6-01
Operation selec-
tion after commu-
nications error
Set the stopping method for com-
munications errors.
0:Deceleration to stop using the
deceleration time in C1-02
1:Coast to stop
2:Emergency stop using the
deceleration time in C1-09
3:Continue operation
0 to 3 1 No A 3A2H –
F6-02
Option card
external fault
detection selec-
tion
0:Always detected
1:Detected only during operation
0 or 1 0 No A 3A3H –
F6-03
Option card
external fault
stopping method
0:Deceleration to stop using the
deceleration time in C1-02
1:Coast to stop
2:Emergency stop using the
deceleration time in C1-09
3:Continue operation
0 to 3 1 No A 3A4H –
F6-05
Current scaling
via communica-
tion option card
Sets the unit of the current monitor
0: Ampere
1: 100% 8192
0 or 1 0 No A 3A6H –