îš‹ Using an Emergency Stop
Set a multi-function input terminal (H1-01 to H1-05) to 15 or 17 (emergency stop) to decelerate to stop using
the deceleration time set in C1-09. If inputting the emergency stop with an NO contact, use setting 15, and if
inputting the emergency stop with an NC contact, use setting 17.
After the emergency stop command has been input, operation cannot be restarted until the Inverter has
stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.
Related parameters
Parameter
Number
Name
Setting
Range
Factory
Setting
Change
during
Operation
Access
Level
C1-09 Emergency stop time
0.0 to
6000.0
10.0 sec. No A