6-110
Digital Operator Functions
îš‹ Setting Digital Operator Functions
Related Parameters
Monitor Selection (o1-01)
Using parameter o1-01 the third monitor item that is directly displayed in Drive Mode can be selected. This
parameter is only effective when the LED Digital Operator is used.
Monitor Display when the Power Supply is Turned ON (o1-02)
Using parameter o1-02 the monitor item (U1-) that is displayed on the Digital Operator when the power
supply is turned ON can be selected.
Parameter
Number
Name
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
o1-01
Monitor selection
*1
*1. This parameter is effective only when the LED Digital Operator is used.
6 to 53 6 Yes A
o1-02 Monitor selection after power up 1 to 4 1 Yes A
o1-03 Digital operator display scaling
0 to
39999
0NoA
o1-09
Frequency reference display unit selection
*2
*2. Parameter function is only valid if a Digital Operator with LCD clear text display is used (LCD or HOA Digital Operator).
0 to 11 0 No A
o2-01
LOCAL/REMOTE key enable/disable
*3
*3. This parameter is effective only when the LED or LCD Digital Operator is used.
0 or 1 1 No A
o2-02
STOP key during control circuit terminal operation
*3
0 or 1 1 No A
o2-03 User parameter initial value 0 to 2 0 No A
o2-05 Frequency reference setting method selection 0 or 1 0 No A
o2-06
Operation selection when digital operator is discon-
nected
0 or 1 0 No A
o2-07 Cumulative operation time setting
0 to
65535
0 hrs No A
o2-08 Cumulative operation time selection 0 or 1 0 No A
o2-09 Initialize Mode 1 to 5 2 No A
o2-10 Fan operation time setting
0 to
65535
0 hr. No A
o2-12 Fault trace initialize 0 or 1 0 No A
o2-14 kWh monitor initialize 0 or 1 0 No A
o2-15
HAND Key function selection
*4
*4. This parameter is effective only when the HOA operator JVOP-162 is used
0 or 1 0 No A