Stopping Methods
6-11
Stopping Methods
This section explains methods of stopping the Inverter.
îš‹ Selecting the Stopping Method when a Stop Command is Input
There are four methods of stopping the Inverter when a stop command is input:
• Deceleration to stop
• Coast to stop
• DC braking stop
• Coast to stop with timer
Set parameter b1-03 to select the Inverter stopping method.
Related Parameters
Parameter
Number
Name
Setting
Range
Factory
Setting
Change
during
Operation
Access
Level
b1-03 Stopping method selection 0 to 3 0 No Q
b2-01
Zero speed level (DC injection braking starting fre-
quency)
0.0 to
10.0
0.5 Hz No A
b2-02 DC injection braking current
0 to
100
50% No A
b2-04 DC injection braking time at stop
0.00
to
10.00
0.50 sec. No A