FWAY/-FWAY: Use this setting.
For a linear actuator with a carrier pin mounted on the ac‐
tuator spindle
In conjunction with devices which use an internal potentiom‐
eter
LWAY/-LWAY: Use this setting for an external linear potenti‐
ometer on a linear actuator (e.g. with cylinder drives).
ncSt/-ncSt: Use this setting for a part-turn actuator for:
An NCS sensor 6DR4004-. N.10 and -.N.40
A positioner 6DR5...-0..9.-....- L1A with internal NCS module
A positioner 6DR59* with accessory NCS module
6DR4004-5L/-5LE
Position Transmitter 6DR4004-2ES, -3ES and -4ES
ncSL/-ncSL: Use this setting for an NCS sensor 6DR4004-.N.20
on a linear actuator for strokes < 14 mm (0.55 inch).
ncSLL/-ncLL: Use this setting for a linear actuator for:
An NCS sensor 6DR4004-.N.30 for strokes > 14 mm
(0.55 inch).
A positioner 6DR5...-0..9.-....- L1A with internal NCS module
A positioner 6DR59* with accessory NCS module
6DR4004-5L/-5LE
Position Transmitter 6DR4004-2ES, -3ES and -4ES
In the case of actuators with inverted direction of action, use the
settings with the minus sign, e.g. -turn.
Description: Meaning of actuator with normal direction of action:
Part-turn actuator closes when the drive shaft, positioner shaft
or magnet of the NCS sensor rotates in the clockwise direction.
Linear actuator closes when the actuator spindle moves down‐
wards and the positioner shaft or magnet of the NCS sensor
rotates in the anti-clockwise direction.
Meaning for actuator with inverted direction of action:
Part-turn actuator closes when the drive shaft, positioner shaft
or magnet of the NCS sensor rotates in the anti-clockwise di‐
rection.
Linear actuator closes when the actuator spindle moves up‐
wards and the positioner shaft or magnet of the NCS sensor
rotates clockwise.
Additional information:
The '3.YWAY' Range of stroke (Page 145) parameter is dis‐
played only for 'WAY', '-WAY', 'ncSLL' or '-ncLL'.
turn/-turn: The '2.YAGL' Rated angle of rotation of feedback
(Page 145) parameter is automatically set to 90° and cannot be
changed.
Parameter assignment
8.4 Description of parameters
SIPART PS2 with 4 to 20 mA/HART
144 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals