EasyManuals Logo
Home>Siemens>Valve Positioners>SIPART PS2 series

Siemens SIPART PS2 series User Manual

Siemens SIPART PS2 series
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #251 background imageLoading...
Page #251 background image
Without explosion protec‐
tion or suitable for use in
Ex "db" version
With explosion protection
Ex "ia"
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-8A 6DR4004-6A 6DR4004-6A
Static destruction limit
± 35 V - -
Connecting to circuits with the fol‐
lowing peak values
- U
i
= DC 25.2 V "ic":
U
i
= DC 25.2 V
"ec"/"tb":
U
n
≤ DC 25.2 V
Effective internal capacitance - C
i
= negligibly small C
i
= negligibly small
Effective internal inductance - L
i
= negligibly small L
i
= negligibly small
Galvanic isolation The three outputs, the BI2 input and the basic device are galvanically isolated from
each other.
Test voltage DC 840 V, 1 s
12.10.2 Analog Output Module (AOM) 6DR4004-6J / -8J
Without explosion protec‐
tion or suitable for use in
Ex d version
With explosion protection
Ex "ia"
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-8J 6DR4004-6J 6DR4004-6J
Direct current output for position feed‐
back
1 current output, terminals 61 and 62 2-wire connection
Rated signal range
4 ... 20 mA, short-circuit proof
Dynamic range
3.6 ... 20.5 mA
Auxiliary power supply U
Aux
+12 ... +35 V +12 ... +30 V +12 ... +30 V
External load R
B
[kΩ]
≤ (U
Aux
[V] - 12 V)/I [mA]
Transmission error
≤ 0.3%
Temperature influence
≤ 0.1%/10 K (≤ 0.1%/18 °F)
Resolution
≤ 0.1%
Residual ripple
≤ 1 %
For connecting to circuits with the
following peak values
- U
i
= DC 30 V
I
i
= 100 mA
P
i
= 1 W
"ic":
U
i
= DC 30 V
I
i
= 100 mA
"ec"/"tb":
U
n
≤ DC 30 V
I
n
≤ 100 mA
P
n
≤ 1 W
Effective internal capacitance - C
i
= 2 nF C
i
= 2 nF
Effective internal inductance - L
i
= 3 μH L
i
= 3 μH
Galvanic isolation Electrically isolated from the alarm option and safely isolated from the basic device
Test voltage DC 840 V, 1 s
Technical data
12.10 Option modules
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE 251

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals