Without explosion protec‐
tion or suitable for use in
Ex "db" version
With explosion protection
Ex "ia"
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-8A 6DR4004-6A 6DR4004-6A
● Static destruction limit
± 35 V - -
● Connecting to circuits with the fol‐
lowing peak values
- U
i
= DC 25.2 V "ic":
U
i
= DC 25.2 V
"ec"/"tb":
U
n
≤ DC 25.2 V
Effective internal capacitance - C
i
= negligibly small C
i
= negligibly small
Effective internal inductance - L
i
= negligibly small L
i
= negligibly small
Galvanic isolation The three outputs, the BI2 input and the basic device are galvanically isolated from
each other.
Test voltage DC 840 V, 1 s
12.10.2 Analog Output Module (AOM) 6DR4004-6J / -8J
Without explosion protec‐
tion or suitable for use in
Ex d version
With explosion protection
Ex "ia"
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-8J 6DR4004-6J 6DR4004-6J
Direct current output for position feed‐
back
1 current output, terminals 61 and 62 2-wire connection
● Rated signal range
4 ... 20 mA, short-circuit proof
● Dynamic range
3.6 ... 20.5 mA
● Auxiliary power supply U
Aux
+12 ... +35 V +12 ... +30 V +12 ... +30 V
● External load R
B
[kΩ]
≤ (U
Aux
[V] - 12 V)/I [mA]
● Transmission error
≤ 0.3%
● Temperature influence
≤ 0.1%/10 K (≤ 0.1%/18 °F)
● Resolution
≤ 0.1%
● Residual ripple
≤ 1 %
● For connecting to circuits with the
following peak values
- U
i
= DC 30 V
I
i
= 100 mA
P
i
= 1 W
"ic":
U
i
= DC 30 V
I
i
= 100 mA
"ec"/"tb":
U
n
≤ DC 30 V
I
n
≤ 100 mA
P
n
≤ 1 W
Effective internal capacitance - C
i
= 2 nF C
i
= 2 nF
Effective internal inductance - L
i
= 3 μH L
i
= 3 μH
Galvanic isolation Electrically isolated from the alarm option and safely isolated from the basic device
Test voltage DC 840 V, 1 s
Technical data
12.10 Option modules
SIPART PS2 with 4 to 20 mA/HART