L1.LIMIT - Limit
Adjustment range: 1 ... 1.00E8
Purpose: Use this sub-parameter to set the base limit for the number of total
strokes. Set the base limit in a range from '1' to '1.00E8'.
Factory setting: 1.00E6
L2.FACT1 - Factor 1
Adjustment range: 0.1 ... 40.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '40.0'. The threshold is the
product of 'L1.LIMIT' and 'L2.FACT1'.
The threshold 1 message is displayed when threshold 1 is excee‐
ded. This message is only output if threshold 2 or 3 is not exceeded
at the same time. The process to activate and display this message
is described in the 'XDIAG' parameter.
Factory setting: 1.0
L3.FACT2 - Factor 2
Adjustment range: 0.1 ... 40.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 2.
Set the factor in a range from '0.1' to '40.0'. The threshold is the
product of 'L1.LIMIT' and 'L3.FACT2'.
The threshold 2 message is displayed when threshold 2 is excee‐
ded. This message is only output if threshold 3 is not exceeded at
the same time. The process to activate and display this message is
described in the 'XDIAG' parameter.
Factory setting: 2.0
L4.FACT3 - Factor 3
Adjustment range: 0.1 ... 40.0
Purpose: Use this sub-parameter to set the factor for formation of threshold 3.
Set the factor in a range from '0.1' to '40.0'. The threshold is the
product of 'L1.LIMIT' and 'L4.FACT3'.
The threshold 3 message is displayed when threshold 3 is excee‐
ded. The process to activate and display this message is described
in the 'XDIAG' parameter.
Factory setting: 5.0
See also
Display of diagnostics values (Page 212)
Parameter assignment
8.4 Description of parameters