12.10 Option modules
12.10.1 Digital I/O Module (DIO) 6DR4004-6A / -8A
Without explosion protec‐
tion or suitable for use in
Ex "db" version
With explosion protection
Ex "ia"
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-8A 6DR4004-6A 6DR4004-6A
3 digital output current circuits
Digital output DO1: Terminals 41 and 42
Digital output DO2: Terminals 51 and 52
Fault message output: Terminals 31 and 32
Auxiliary power supply U
Aux
35 V and the current con‐
sumption is to be limited to
< 25 mA
- -
Signal status
High (not addressed) Conductive, R = 1 kΩ,
+3/-1 % *)
≥ 2.1 mA ≥ 2.1 mA
Low *) (addressed) Deactivated, I
R
< 60 µA ≤ 1.2 mA ≤ 1.2 mA
*) The status is also Low if the
basic device is faulty or without
a auxiliary power.
*) When using in the flame‐
proof enclosure, the cur‐
rent consumption must be
restricted to 10 mA per out‐
put.
Switching threshold for
supply according to
EN 60947-5-6:
U
Aux
= 8.2 V, R
i
= 1 kΩ
Switching threshold for
supply according to
EN 60947-5-6:
U
Aux
= 8.2 V, R
i
= 1 kΩ
For connecting to circuits with the
following peak values
- U
i
= 15 V DC
I
i
= 25 mA
P
i
= 64 mW
"ic":
U
i
= 15 V DC
I
i
= 25 mA
"ec"/"tb":
U
n
≤ 15 V DC
Effective internal capacitance - C
i
= 5.2 nF C
i
= 5.2 nF
Effective internal inductance - L
i
= negligibly small L
i
= negligibly small
1 digital input current circuit
Digital input DI2: Terminals 11 and 12, terminals 21 and 22 (jumper)
Galvanically connected with the
basic device
Signal status 0 Floating contact, open
Signal status 1 Floating contact, closed
Contact load 3 V, 5 μA
Electrically isolated from the basic
device
Signal status 0 ≤ 4.5 V or open
Signal status 1 ≥ 13 V
Internal resistance ≥ 25 kΩ
Technical data
12.10 Option modules
SIPART PS2 with 4 to 20 mA/HART
250 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals