59 mA Setpoint current 0.0 ... 20.0 mA â‘¡
60 PZ Supply pressure (PZ) 99.999 (bar)
999.99 (psi)
9.9999 (MPa)
- â‘¢
63 PZMAX Supply pressure (PZ) min/max pointer - â‘
64 N_MIN Event counter 0 ... 99999 - â‘
11.2.4 Meaning of the diagnostics values
11.2.4.1 Diagnostic value '1.STRKS - Number of total strokes'
Display range: 0 ... 4.29E9
Purpose: In operation, the movements of the actuator are summed up and
displayed in this diagnostics parameter as the number of strokes.
Unit: 100% strokes, i.e. the path between 0% and 100% and back.
11.2.4.2 Diagnostic value '2.CHDIR - Number of changes in direction'
Display range: 0 ... 4.29E9
Purpose: Every change in direction of the actuator is noted in the controller
and added to the number of changes in direction.
11.2.4.3 Diagnostic value '3.\\CNT - Number of fault messages'
Display range: 0 ... 4.29E9
Purpose: Every fault is noted in the closed-loop controller with '3. CNT' and
added to the number of fault messages.
11.2.4.4 Diagnostic value '4.A1CNT - Number of alarms 1' / '5.A2CNT - Number of alarms 2'
Requirement: '44.AFCT' Alarm function (Page 156) parameter is activated.
Display range: 0 ... 4.29E9
Purpose: This value indicates how often the alarm has been triggered.
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE 215