J3.LEVL2 - threshold 2
Adjustment range: -40.0C ... 90.0C
-40.0F ... 194.0F
Purpose: Use this sub-parameter to set the temperature for threshold 2.
The positioner triggers a threshold 2 message if the current tem‐
perature inside the enclosure exceeds threshold 2. This message is
only output if threshold 3 is not exceeded at the same time. The
process to activate and display this message is described in the
'XDIAG' parameter.
Factory setting: 80.0C
J4.LEVL3 - threshold 3
Adjustment range: -40.0C ... 90.0C
-40.0F ... 194.0F
Purpose: Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a threshold 3 message if the current tem‐
perature inside the enclosure exceeds threshold 3. The process to
activate and display this message is described in the 'XDIAG' pa‐
rameter.
Factory setting: 90.0C
8.4.3.10 Monitoring of number of total strokes 'L.\\STRK'
L. STRK - Monitoring of number of total strokes
Condition: The '52.XDIAG' Activating for extended diagnostics (Page 162) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
Possible settings: OFF
On
Purpose: Use this parameter to continuously monitor the total strokes cov‐
ered by the actuator. A total stroke corresponds to the path from the
lower endstop of the actuator to the upper endstop and back again,
in other words twice the travel. During operation, partial strokes of
the actuator are added together into total strokes. Monitoring is
performed in three steps. To activate monitoring, set the parameter
to 'On'. Sub-parameters are displayed. Appropriately set the sub-
parameters.
The current value is displayed in Diagnostic value '1.STRKS - Num‐
ber of total strokes' (Page 215). The positioner triggers a message
if the current value exceeds one of the three thresholds. This mes‐
sage is only output if threshold 2 or 3 is not exceeded at the same
time.
Factory setting: OFF
Parameter assignment
8.4 Description of parameters
SIPART PS2 with 4 to 20 mA/HART
182 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals