EasyManuals Logo
Home>Siemens>Valve Positioners>SIPART PS2 series

Siemens SIPART PS2 series User Manual

Siemens SIPART PS2 series
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
8.4.2.20 '50.PRST' Preset
Possible settings: ALL
Init
PArA
diAg
Purpose: Use this parameter to restore the factory settings for most parame‐
ters. The following parameter groups are available:
ALL: Reset all parameters together which can be reset by 'Init',
'PArA' and 'diAg'.
Init: Reset initialization parameters '1.YFCT' to '5.INITM'.
PArA: Reset application parameters '6.SCUR' Current range of
setpoint (Page 147) to '49.\\LIM' Response threshold of fault
message 'Control deviation' (Page 159).
diAg: Resetting the extended diagnostic parameters A to U
(Page 163) as well as parameter '52.XDIAG' Activating for ex‐
tended diagnostics (Page 162).
An overview of the parameters and factory settings can be found in
section Tabular overview of the parameters (Page 135).
In order to select one of the parameter groups listed above, repeat‐
edly press the button until the desired setting is output in the
display. Start the function by keeping the button pressed until
'oCAY' is output in the display. The values of the parameter group
are now the factory settings.
Description: If you wish to use a previously initialized positioner on a different
control valve, set the parameters to the factory settings prior to a
new initialization. To do this, use the 'ALL' or 'Init' setting.
Restore the factory settings if you have changed several parameters
at once without being able to predict their effect and the undesired
reactions which may occur as a result. To do this, use the 'ALL'
setting.
Factory setting: ALL
See also
Display of diagnostics values (Page 212)
8.4.2.21 '51.PNEUM' Pneumatics type
Requirements: FIP You have a positioner with the "Fail in place" function with
order suffix -Z, order code F01.
booSt You operate the positioner with a booster.
Possible settings: Std Standard pneumatic block
FIP Fail in place pneumatic block
booSt Operation with boosters
Parameter assignment
8.4 Description of parameters
SIPART PS2 with 4 to 20 mA/HART
160 Operating Instructions, 11/2019, A5E00074631-AE

Table of Contents

Other manuals for Siemens SIPART PS2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 series and is the answer not in the manual?

Siemens SIPART PS2 series Specifications

General IconGeneral
BrandSiemens
ModelSIPART PS2 series
CategoryValve Positioners
LanguageEnglish

Related product manuals